Hanna Auto Doser Controller Parameters

 

pH Setup

Dose Type  Acid
Set Point 7.35
Proportional Band  0.4 pH
pH Flow Rate  1.0 L/h
Overtime  60 min
Alarm High  8.5 pH
Alarm High Enabled
Alarm Low 6.5 pH
Alarm Low Enabled
Warnings and Errors Enabled
Startup Dosing Delay. 4 min
Analog Out A01
Max Analog Out 12pH
Min Analog Out 2 pH
Acid Tank Input Disabled

 

ORP Setup                      

Set Point 735mv
Proportional Band  70mv
Cl2 Flow Rate  1.0 L/h
Overtime  60 min
Alarm High  950mv
Alarm High Enabled
Alarm Low 350mv
Alarm Low Enabled
Warnings and Errors Enabled
Alarm Activates Relay Enabled
Startup Dosing Delay 4 min
Analog Out A02
Analog Max 2000mv
Analog Min 0mv
Cl2 Tank Input Disabled

 

Temp Settings

Alarm High  110
Alarm High Enabled
Alarm Low 35
Alarm Low Enabled
Warnings and Errors Enabled
Alarm Activates relay Enabled
Unit Fahrenheit
Analog Out A03
Analog Max 221.0 F
Analog Min 23.0F

 

General Settings

Date/Time -Set at Plunge-
Unit ID -Set at Plunge-
Key Beep Enabled
Hold Input Enabled